WOBBLheatsink.py

Does a 30 W chip stay under 85 C with a 10 CFM, 20 Pa fan blowing along the fins in a 40 C cabinet?

Heat report
2026-10-15 18:29
OK

With 232 L/min of air through its duct, the faces shed heat at 29.8 W/(m2 K) on average, and 30 W brings the hottest point to 77 C against a limit of 85 C.

max temperature
77 C
limit
85 C
mean h
29.8 W/m2K
pressure drop
4.05 Pa
flow
232 L/min

Confidence low

  • grid convergence failed: pressure drop 3.539 -> 3.868 -> 4.045 Pa over 3 grids, grid convergence index 32% (observed order 2, extrapolated 4.473 Pa), so the grid is too coarse for this answer
  • residuals: largest final residual 0.0032 (k), every field fell at least 1.4 orders, close to converged, so the key number may still move slightly
  • wall resolution: y+ on the walls averages 6.53, at most 11.3, for wall functions, so part of the wall sits in the buffer layer, where wall functions are least accurate, though the blended wall function keeps the error to a few percent
  • operating point: the curve gives 3.58 Pa at 232 L/min, and the fine grid needs 4.05 Pa there (13% apart), so the coarse grid's fit set the flow a little off
  • hand calculation: heat balance on a uniform skin gives 69.2 C; the FEA skin averages 72.6 C (12% of the rise). Biot 0.00013: the part is nearly isothermal
  • convective heat transfer from RANS is commonly within 10 to 25% of measurements

Simulation

The part's temperature with the hottest point marked
The part's temperature with the hottest point marked
Pressure on the part's walls
Pressure on the part's walls

Checks

statuscheckresult
passmesh quality102,204 cells, worst non orthogonality 37 degrees and skewness 0.39
failgrid convergencepressure drop 3.539 -> 3.868 -> 4.045 Pa over 3 grids, grid convergence index 32% (observed order 2, extrapolated 4.473 Pa), so the grid is too coarse for this answer
passiterative convergencepressure drop swings 0.0061% over the last fifth of 153 iterations
passmass conservationin 0.00387 m3/s, out 0.00387 m3/s (2.1e-05% apart)
warnresidualslargest final residual 0.0032 (k), every field fell at least 1.4 orders, close to converged, so the key number may still move slightly
warnwall resolutiony+ on the walls averages 6.53, at most 11.3, for wall functions, so part of the wall sits in the buffer layer, where wall functions are least accurate, though the blended wall function keeps the error to a few percent
passflow regimeRe 6361 on the inlet's hydraulic diameter, turbulent
infohand calculationa straight smooth duct of the same 60 mm hydraulic diameter and 60 mm length loses 0.0634 Pa by Colebrook, and the part loses 4.05 Pa, 63.86 times that, the rest from turns, junctions and changes of section
warnoperating pointthe curve gives 3.58 Pa at 232 L/min, and the fine grid needs 4.05 Pa there (13% apart), so the coarse grid's fit set the flow a little off
passmesh convergencetemperature rise at the hottest point settled: 37.1 -> 36.9 -> 37 C over 3 meshes, last change 0.4%
passenergy balanceheat in 30 W, heat out through the surfaces 30 W (1.1e-07% apart)
warnhand calculationheat balance on a uniform skin gives 69.2 C; the FEA skin averages 72.6 C (12% of the rise). Biot 0.00013: the part is nearly isothermal
passunits and sanitytemperatures between 70.7 and 77 C; radiation is off, it could shed up to about 11.6 W at this temperature (pass --radiation 0.9 for painted or plastic surfaces)
infolumped estimatethe wetted area of 331 cm2 at the mean 29.8 W/(m2 K) puts a part at one temperature at 73.8 C, and the FEA's hottest point is 77 C
infoheat transfer correlationGnielinski's correlation for a straight tube gives 9.35 W/(m2 K) at Re 6361 on the 60 mm hydraulic diameter, and the CFD averages 29.8 W/(m2 K) over the wetted faces, which include entrance regions and turns that raise it

Assumptions

  1. Wobbl guessed: The stream runs along (+0.00, +1.00, +0.00) in the part's coordinates.
  2. Wobbl guessed: The part has no passage of its own, so it sits in a duct of its own cross section, the way a shroud carries a fan's air through a heat sink.
  3. Air at 40 C, density 1.127 kg/m3, viscosity 1.907e-05 Pa s, conductivity 0.0272 W/(m K), Prandtl 0.704.
  4. The stream runs along (+0.00, +1.00, +0.00) in the part's coordinates.
  5. The part has no passage of its own, so it sits in a duct of its own cross section, the way a shroud carries a fan's air through a heat sink.
  6. Steady, incompressible flow with the k omega SST turbulence model and blended wall functions.
  7. Meshed by snappyHexMesh with 102,204 cells on the finest of 3 grids, without boundary layer cells.
  8. The fluid enters at 40 C and warms by 6.83 C, so the films use 43.4 C.
  9. Each face's heat transfer coefficient comes from the CFD with the walls at one uniform temperature, and faces the flow does not reach get still air at 5 W/(m2 K).
  10. One way coupling, so the fluid's properties do not change with the part's temperature.
  11. Aluminum 6063-T5: conductivity 209 W/(m K), specific heat 900 J/(kg K), density 2700 kg/m3.
  12. Heat enters through bottom and box 17.5,17.5,-1,42.5,42.5,0.5.
  13. Surrounding air or coolant at 40 C does not heat up.
  14. Radiation is ignored (conservative).
  15. Contact resistance between parts and internal airflow are not modeled.