knx
tested on simulator
| Tier | Tier 3 |
|---|---|
| Protocol | KNXnet/IP tunneling, KNXnet/IP tunneling over TCP, KNXnet/IP routing |
| Covers | KNX switch and dimmer actuators, KNX blind actuators, KNX room thermostats, KNX sensors and weather stations, KNX scene and HVAC controllers |
| Hazard default | low |
| Conformance | control |
| Tested with | real xknx tunneling against a fake KNXnet/IP server built from xknx's frame classes, with a simulated room |
Estimated reach. Thousands of certified products. KNX is a single standard across hundreds of manufacturers, and every certified device communicates in group telegrams with standard datapoint types, which this driver maps from a group address list. KNX Secure devices and device programming are not covered, and the group addresses must come from the installation's ETS project.
The knx driver reads and sets KNX group addresses through a KNXnet/IP interface or router with xknx. Channels come from the ETS group address list, each with a group address and a datapoint type.
Supports
- Tunneling over UDP or TCP, and routing over multicast.
- DPT 1.x bools, numeric DPTs such as 5.001, 7.x, 9.x, 13.x and 14.x, enum DPTs such as 20.102 with lower case names like
comfort, and DPT 16 strings. - DPT units convert to the channel unit.
discover()sends a SEARCH_REQUEST, which only requests interface descriptions.
Setup
uv tool install --compile-bytecode "halkit[knx] @ git+https://github.com/sohan-bhat/OpenHAL"KNX Secure isn't supported yet, so enable a plain tunnel for the hub.
| Parameter | Default | Meaning |
|---|---|---|
gateway | required | Interface address for tunneling, or the multicast group for routing. knx: 192.168.1.20 is shorthand |
port | 3671 | KNXnet/IP port |
connection | tunneling | tunneling, tunneling_tcp or routing |
local_ip | automatic | Hub address on the KNX network |
individual_address | from the interface | Hub individual address, needed for routing |
route_back | false | Tunneling through NAT |
timeout | 2 s | Read response deadline |
Channel maps
read:
temperature: { unit: degC, map: { group_address: 3/1/0, dpt: "9.001" } }
write:
ceiling_light: { type: bool, map: { group_address: 1/1/0, dpt: "1.001", state_address: 1/1/1 } }
ceiling_dimmer: { unit: percent, min: 0, max: 100, map: { group_address: 1/1/2, dpt: "5.001", state_address: 1/1/3 } }| Key | Meaning |
|---|---|
group_address | Address read or sent to, three-level 1/2/3, two-level 1/2 or free 4660 |
dpt | Quoted datapoint type such as "9.001", since YAML reads an unquoted 5.010 as 5.01 |
state_address | Control channels. Actuator status address for read-back |
Behavior
- Reads return the newest telegram, or send one GroupValueRead when nothing has arrived. An address with the read flag off reads as no value.
- A command confirms only that the telegram reached the bus, so read the
state_addressto check the actuator. - Values round to the DPT resolution, such as 51 % for 50.4 %.
- A lost tunnel leaves the device unavailable until the hub reconnects, so nothing goes out late.
- Bad DPTs and malformed addresses fail at load. Values a DPT can't carry are never sent.
Example
openhal/drivers/knx/examples/living-room.hal.yaml switches and dims a ceiling light, sets the heating setpoint and HVAC mode, and keeps the setpoint low while a window is open.
Limitations
- No KNX Secure, device programming or ETS project import.
describe()returns nothing, since KNX devices can't list their addresses.- One telegram at a time per file, as the bus carries about 50 a second.
Hazard default and safe state
Low. safe_state_support is file. Set each actuator's bus failure behavior in ETS as the real fallback.