opcua

tested on simulator

Tier Tier 2
Protocol OPC UA binary over TCP (opc.tcp)
Covers PLCs with an OPC UA server, LADS lab instruments, process equipment and gateways
Hazard default medium
Conformance full
Tested with asyncua's own OPC UA server running a simulated pump skid

Estimated reach. Thousands of controller and instrument models. OPC UA is the standard interface of industrial automation. Most current PLC families include an OPC UA server, and the LADS companion specification brings it to laboratory instruments. The driver reads and changes variables and calls methods, which covers any server that exposes its data that way. The count is a model estimate.

The opcua driver connects to OPC UA servers, the interface of most current PLCs, process equipment and LADS lab instruments, with asyncua 2.1.0. Variables become channels with their engineering units, methods become actions, and describe browses the Objects folder.

Supports

Every channel and action names a node in a map.

MapMeaning
{ node: "ns=2;s=Pump.Speed" }A variable, read, or set when the file's write section names the variable
{ node: "nsu=urn:example:skid;s=Pump.Speed" }The same with the namespace URI instead of the index
{ node: "ns=2;s=Tank.Level", unit: percent, scale: 100 }unit overrides EngineeringUnits, scale multiplies the value
{ object: "ns=2;s=Pump", method: "ns=2;s=Pump.Start", inputs: [rate] }A method call, with inputs in the method's argument order

Node ids may be numeric i=2258, string s=..., GUID g=... or opaque b=.... nsu= ids resolve against the namespace array on connect, so renumbered namespaces keep working.

How the protocol is handled

  • connect() checks that every variable exists, that write variables are writable for this user, and that methods exist with the listed input count.
  • Units come from EngineeringUnits by UNECE code, such as CEL, KPA, RPM, P1 and about 45 more, or by display name. A unit that can't convert fails the connect, so a degF node can't read as degC.
  • Bad status fails a read. Uncertain status, or a value outside range, marks the reading suspect.
  • Changes go out as the node's own data type. Fractional or out-of-range values for integer nodes are blocked.
  • Method arguments go out as the declared input types, in each argument's declared unit.

Safe state

OPC UA has no general stop, so give the file a safe_state with the equipment's own stop, such as a Stop method and zero setpoints. The steps run in order on every stop.

Discovery

openhal discover calls FindServers on opc.tcp://127.0.0.1:4840 and lists the registered servers without reading or changing anything.

Setup

  1. Install with uv tool install --compile-bytecode "halkit[opcua] @ git+https://github.com/sohan-bhat/OpenHAL".
  2. Find the endpoint URL and node ids with the PLC's tool or a client such as UaExpert.
  3. Start from openhal/drivers/opcua/examples/dosing-pump.hal.yaml or describe.
KeyDefaultMeaning
endpointrequiredopc.tcp://host:port/path
timeout4 sPer request
usernoneUser name for username login
token_envnoneVariable holding the password for user
securitynoneasyncua security string, such as Basic256Sha256,SignAndEncrypt,client.der,client.pem
browse_depth3Object levels describe browses

Known limitations

  • No subscriptions, so each read is one request at the hub's poll rate.
  • No arrays, structures or enumerated data types beyond String, numbers and Boolean.
  • Without EURange, describe sets numeric limits of 0 to 0 until a person sets real ones.
  • asyncua is LGPL-3.0, installed separately, unmodified and not copied.

Hazard defaults

medium, since PLCs drive pumps, heaters, valves and motors. Use high for anything that can injure, and keep the PLC's own interlocks and e-stop circuit.

Sources